Isolated Shunt Amplifier Module (Isam)
Introduction
A standard MiniCSU system only accepts Hall-effect current transducers
with full scale output of ± 4V. In
situations where current shunts are used in place of Hall-effect current
transducers, the ISAM, or Isolated Shunt Amplifier Module can be used. It
provides optical isolation and converts the ± 75mV current shunt full scale signal to the required ± 4V full scale signal.
Electrical Specification
Electrical Specification
Power Supply ± 14Vdc to ± 16Vdc
Signal Input ± 75mV
Input Impedance 650
W
Absolute Max Input ± 6V
Signal Output ± 4V (@ ± 75mV input)
Output Impedance 1
kW
Output Short Circuit Indefinite
Output Error Typically
0.1% of 4V FSD
Output Zero Offset Typically
0.1% of 4V FSD
Physical Specification
Board Dimensions approx. 116mm x 66mm
Signal Input Connector 2 pin male header 5.0mm
pitch
Output Connector 4 pin male header 2.54mm
pitch
Input connections Shunt
+, Shunt -
Output Connections +15V,
-15V, VOUT, GND
System Setup
The ISAM should be located
as close as possible to the shunt, ideally within 1~2 meters of the shunt. It
should also be mounted securely in a dry, dust free environment. The shunt
should be wired up to 2 way Weco 5.0mm screw connector ,
polarity is shown below:
|
|||
Wire up a Molex 22-01-2045
Female connector with the following connections:
|
|||
The other side of the 4-way
cable can be connected either to the MUIB or MUIB2.